BN3000

BN3000

BN3000

Measurement per phase, network-capable and multifunctional
  • Measurement per phase via network
  • Display with rotatable screen
  • Optional technology modules such as RCM type B
  • Cost benefit through Master/Slave cascading

Measurement per phase, network-capable and multifunctional

The BN3000 is an intelligent PDU (Power Distribution Unit). As with the BN2000, it enables measurements for each phase at PDU level via the network. It is also equipped with additional intelligent functions, therefore enabling professional energy and capacity management.

Thanks to its compact design (1U), installing the BN3000 is flexible and space-saving, and enables optimised cabling and air flow in the server rack.

Whether on-site or remotely via Ethernet: energy consumption measurements can be viewed locally on the display or via the web server using the clear and highly functional software interface. Furthermore, the BN3000 can be integrated into corresponding software systems via SNMP or Modbus TCP, for example. Granular measurement recording accompanied by neutral conductor monitoring and RCM type B (as an option) ensures maximum safety in the data centre. In addition, intelligent Master/Slave cascading in the PDU network enables cost-optimised network management.

The following measurement values are displayed per phase on the illuminated display and in the integrated web server:

    • Current [A]

    • Neutral conductor current [A] for three-phase versions]

    • Voltage [V]

    • Frequency [Hz]]

    • Active power [kW]

    • Reactive power [kVAr]

    • Apparent power [kVA]

    • Active energy [kWh]

    • Reactive energy [kVArh]

    • Apparent energy [kVAh]

    • Power factor]

    Furthermore, the flexible design of the PDU and different technology modules make a multitude of customised versions possible.

    Optional technology modules:

    Residual Current Monitoring (RCM type B) AC [mA] and DC [mA], Surge Protection Device (SPD), GPIO module, housing colour, temperature and air humidity sensors

    This PDU is available as a 19" version or for vertical installation.

    Further product configurations available on request.

    BN3000

    BN3000 (230-400 V / 50 Hz) | incl. mounting kit

    16 A / 230 V

    16 A / 230 V

    Number of socket outlets with earthing contact
    Number of C13 sockets
    Number of C19 sockets

    Outlets Gesamt

    Stecker

    Kabeltyp

    Leitungsschutzschalter

    Maße

    16 A / 230 V

    802.3006
    Number of socket outlets with earthing contact 4
    Number of C13 sockets 16
    Number of C19 sockets

    16 A / 230 V

    0

    16 A / 230 V

    CEE 16A

    16 A / 230 V

    H05VV-F 3G 2,50 mm²

    16 A / 230 V

    16 A / 230 V

    1102 x 44 x 65 mm

    16 A / 230 V

    802.3004
    Number of socket outlets with earthing contact
    Number of C13 sockets 16
    Number of C19 sockets 4

    16 A / 230 V

    0

    16 A / 230 V

    CEE 16A

    16 A / 230 V

    H05VV-F 3G 2,50 mm²

    16 A / 230 V

    16 A / 230 V

    1102 x 44 x 65 mm

    16 A / 230 V

    802.3041
    Number of socket outlets with earthing contact
    Number of C13 sockets 24
    Number of C19 sockets 4

    16 A / 230 V

    0

    16 A / 230 V

    CEE 16A

    16 A / 230 V

    H05VV-F 3G 2,50 mm²

    16 A / 230 V

    16 A / 230 V

    1533 x 44 x 65 mm
    Show more

    16 A / 230 V / Residual Current Monitoring per supply cable

    16 A / 230 V / Residual Current Monitoring per supply cable

    Number of socket outlets with earthing contact
    Number of C13 sockets
    Number of C19 sockets

    Outlets Gesamt

    Stecker

    Kabeltyp

    Leitungsschutzschalter

    Maße

    16 A / 230 V / Residual Current Monitoring per supply cable

    802.3055
    Number of socket outlets with earthing contact
    Number of C13 sockets 16
    Number of C19 sockets 4

    16 A / 230 V / Residual Current Monitoring per supply cable

    0

    16 A / 230 V / Residual Current Monitoring per supply cable

    CEE 16A

    16 A / 230 V / Residual Current Monitoring per supply cable

    H05VV-F 3G 2,50 mm²

    16 A / 230 V / Residual Current Monitoring per supply cable

    16 A / 230 V / Residual Current Monitoring per supply cable

    1103 x 44 x 65 mm
    Show more

    16 A / 400 V

    16 A / 400 V

    Number of socket outlets with earthing contact
    Number of C13 sockets
    Number of C19 sockets

    Outlets Gesamt

    Stecker

    Kabeltyp

    Leitungsschutzschalter

    Maße

    16 A / 400 V

    802.3014
    Number of socket outlets with earthing contact 6
    Number of C13 sockets 24
    Number of C19 sockets

    16 A / 400 V

    0

    16 A / 400 V

    CEE 16A

    16 A / 400 V

    H05VV-F 5G 2,50 mm²

    16 A / 400 V

    16 A / 400 V

    1533 x 44 x 65 mm

    16 A / 400 V

    802.3016
    Number of socket outlets with earthing contact 6
    Number of C13 sockets 24
    Number of C19 sockets 6

    16 A / 400 V

    0

    16 A / 400 V

    CEE 16A

    16 A / 400 V

    H05VV-F 5G 2,50 mm²

    16 A / 400 V

    16 A / 400 V

    1762 x 44 x 65 mm

    16 A / 400 V

    802.3012
    Number of socket outlets with earthing contact
    Number of C13 sockets 24
    Number of C19 sockets 6

    16 A / 400 V

    0

    16 A / 400 V

    CEE 16A

    16 A / 400 V

    H05VV-F 5G 2,50 mm²

    16 A / 400 V

    16 A / 400 V

    1533 x 44 x 65 mm
    Show more

    16 A / 400 V / Residual Current Monitoring per phase

    16 A / 400 V / Residual Current Monitoring per phase

    Number of socket outlets with earthing contact
    Number of C13 sockets
    Number of C19 sockets

    Outlets Gesamt

    Stecker

    Kabeltyp

    Leitungsschutzschalter

    Maße

    16 A / 400 V / Residual Current Monitoring per phase

    802.3023
    Number of socket outlets with earthing contact 3
    Number of C13 sockets 18
    Number of C19 sockets

    16 A / 400 V / Residual Current Monitoring per phase

    0

    16 A / 400 V / Residual Current Monitoring per phase

    CEE 16A

    16 A / 400 V / Residual Current Monitoring per phase

    H05VV-F 5G 2,50 mm²

    16 A / 400 V / Residual Current Monitoring per phase

    16 A / 400 V / Residual Current Monitoring per phase

    1500 x 44 x 65 mm

    16 A / 400 V / Residual Current Monitoring per phase

    802.3022
    Number of socket outlets with earthing contact
    Number of C13 sockets 18
    Number of C19 sockets 3

    16 A / 400 V / Residual Current Monitoring per phase

    0

    16 A / 400 V / Residual Current Monitoring per phase

    CEE 16A

    16 A / 400 V / Residual Current Monitoring per phase

    H05VV-F 5G 2,50 mm²

    16 A / 400 V / Residual Current Monitoring per phase

    16 A / 400 V / Residual Current Monitoring per phase

    1234 x 44 x 65 mm

    16 A / 400 V / Residual Current Monitoring per phase

    802.3024
    Number of socket outlets with earthing contact
    Number of C13 sockets 24
    Number of C19 sockets 6

    16 A / 400 V / Residual Current Monitoring per phase

    0

    16 A / 400 V / Residual Current Monitoring per phase

    CEE 16A

    16 A / 400 V / Residual Current Monitoring per phase

    H05VV-F 5G 2,50 mm²

    16 A / 400 V / Residual Current Monitoring per phase

    16 A / 400 V / Residual Current Monitoring per phase

    1533 x 44 x 65 mm
    Show more

    16 A / 400 V / Residual Current Monitoring per supply cable

    16 A / 400 V / Residual Current Monitoring per supply cable

    Number of socket outlets with earthing contact
    Number of C13 sockets
    Number of C19 sockets

    Outlets Gesamt

    Stecker

    Kabeltyp

    Leitungsschutzschalter

    Maße

    16 A / 400 V / Residual Current Monitoring per supply cable

    802.3030
    Number of socket outlets with earthing contact
    Number of C13 sockets 24
    Number of C19 sockets 12

    16 A / 400 V / Residual Current Monitoring per supply cable

    0

    16 A / 400 V / Residual Current Monitoring per supply cable

    CEE 16A

    16 A / 400 V / Residual Current Monitoring per supply cable

    H05VV-F 5G 2,50 mm²

    16 A / 400 V / Residual Current Monitoring per supply cable

    16 A / 400 V / Residual Current Monitoring per supply cable

    1762 x 44 x 65 mm
    Show more

    32 A / 230 V

    32 A / 230 V

    Number of socket outlets with earthing contact
    Number of C13 sockets
    Number of C19 sockets

    Outlets Gesamt

    Stecker

    Kabeltyp

    Leitungsschutzschalter

    Maße

    32 A / 230 V

    802.3005
    Number of socket outlets with earthing contact
    Number of C13 sockets 16
    Number of C19 sockets 4

    32 A / 230 V

    0

    32 A / 230 V

    CEE 32A

    32 A / 230 V

    H05VV-F 3G 4,00 mm²

    32 A / 230 V

    2 x C16A

    32 A / 230 V

    1234 x 44 x 65 mm
    Show more

    32 A / 400 V

    32 A / 400 V

    Number of socket outlets with earthing contact
    Number of C13 sockets
    Number of C19 sockets

    Outlets Gesamt

    Stecker

    Kabeltyp

    Leitungsschutzschalter

    Maße

    32 A / 400 V

    802.3013
    Number of socket outlets with earthing contact
    Number of C13 sockets 24
    Number of C19 sockets 6

    32 A / 400 V

    0

    32 A / 400 V

    CEE 32A

    32 A / 400 V

    H05VV-F 5G 4,00 mm²

    32 A / 400 V

    6 x C16A

    32 A / 400 V

    1762 x 44 x 65 mm

    32 A / 400 V

    802.3019
    Number of socket outlets with earthing contact
    Number of C13 sockets 36
    Number of C19 sockets 6

    32 A / 400 V

    0

    32 A / 400 V

    CEE 32A

    32 A / 400 V

    H05VV-F 5G 4,00 mm²

    32 A / 400 V

    6 x C16A

    32 A / 400 V

    2170 x 44 x 65 mm
    Show more

    32 A / 400 V / Residual Current Monitoring per phase

    32 A / 400 V / Residual Current Monitoring per phase

    Number of socket outlets with earthing contact
    Number of C13 sockets
    Number of C19 sockets

    Outlets Gesamt

    Stecker

    Kabeltyp

    Leitungsschutzschalter

    Maße

    32 A / 400 V / Residual Current Monitoring per phase

    802.3025
    Number of socket outlets with earthing contact
    Number of C13 sockets 24
    Number of C19 sockets 6

    32 A / 400 V / Residual Current Monitoring per phase

    0

    32 A / 400 V / Residual Current Monitoring per phase

    CEE 32A

    32 A / 400 V / Residual Current Monitoring per phase

    H05VV-F 5G 4,00 mm²

    32 A / 400 V / Residual Current Monitoring per phase

    6 x C16A

    32 A / 400 V / Residual Current Monitoring per phase

    1873 x 44 x 65 mm
    Show more

    32 A / 400 V / Residual Current Monitoring per supply cable

    32 A / 400 V / Residual Current Monitoring per supply cable

    Number of socket outlets with earthing contact
    Number of C13 sockets
    Number of C19 sockets

    Outlets Gesamt

    Stecker

    Kabeltyp

    Leitungsschutzschalter

    Maße

    32 A / 400 V / Residual Current Monitoring per supply cable

    802.3031
    Number of socket outlets with earthing contact
    Number of C13 sockets 24
    Number of C19 sockets 12

    32 A / 400 V / Residual Current Monitoring per supply cable

    0

    32 A / 400 V / Residual Current Monitoring per supply cable

    CEE 32A

    32 A / 400 V / Residual Current Monitoring per supply cable

    H05VV-F 5G 4,00 mm²

    32 A / 400 V / Residual Current Monitoring per supply cable

    6 x C16A

    32 A / 400 V / Residual Current Monitoring per supply cable

    2037 x 44 x 65 mm
    Show more

    Ask for your desired product!

    Do you need more information about our products and services? Please feel free to contact us.

    map

    Questions? We will help you!

    Do you have questions or would you like a quote? We will be happy to help you.

    It's easy to find your local consultant.

    Telephone number

    +49 711 86602-0

    Applications

    Professional

    learn more

    IT Infrastructure

    learn more

    References

    learn more