BN3500

BN3500

BN3500

Measurement per phase and outlet, network-ca- pable and multifunctional
  • Measurement per phase and outlet
  • Display with rotatable screen
  • Optional technology modules such as RCM type B
  • Cost benefit through Master/Slave cascading

Measurement per phase and outlet, network-capable and multifunctional

The BN3500 is an intelligent PDU (Power Distribution Unit). As with the BN3000, it enables professional energy and capacity management through network-capable measurements for each phase at PDU level. In addition, measurement values per outlet can be monitored.

Thanks to its compact design (1U), installing the BN3500 is flexible and space-saving, and therefore enables optimised cabling and air flow in the server rack.

Whether on-site or remotely via Ethernet: energy consumption measurements can be viewed locally on the display or via the web server using the clear and highly functional software interface. Furthermore, the BN3500 can be integrated into third-party software systems via SNMP or Modbus TCP, for example.

Granular measurement recording accompanied by neutral conductor monitoring and RCM type B (as an option) ensures maximum safety in the data centre. In addition, intelligent Master/Slave cascading in the PDU network enables cost-optimised network management.

The following measurement values are displayed for each phase and outlet on the illuminated display and in the integrated web server:

    • Current [A]

    • Neutral conductor current [A] for three-phase versions]

    • Voltage [V]

    • Frequency [Hz]]

    • Active power [kW]

    • Reactive power [kVAr]

    • Apparent power [kVA]

    • Active energy [kWh]

    • Reactive energy [kVArh]

    • Apparent energy [kVAh]

    • Power factor]

    Furthermore, the flexible design of the PDU and different technology modules make a multitude of customised versions possible.

    Optional technology modules:

    Residual Current Monitoring (RCM type B) AC [mA] and DC [mA], Surge Protection Device (SPD), GPIO module, housing colour, temperature and air humidity sensors

    This PDU is available as a 19" version or for vertical installation.

    Further product configurations available on request.

    BN3500

    BN3500 (230-400 V / 50 Hz) | incl. mounting kit

    16 A / 230 V

    16 A / 230 V

    Number of C13 sockets
    Number of C19 sockets

    Outlets in total

    Slave variant

    For at least 46U server racks

    Plug

    Dimensions

    16 A / 230 V

    802.3500
    Number of C13 sockets 18
    Number of C19 sockets 4

    16 A / 230 V

    0

    16 A / 230 V

    -

    16 A / 230 V

    -

    16 A / 230 V

    CEE 16A

    16 A / 230 V

    1234 x 44 x 65 mm

    16 A / 230 V

    802.3519
    Number of C13 sockets 24
    Number of C19 sockets 4

    16 A / 230 V

    0

    16 A / 230 V

    -

    16 A / 230 V

    -

    16 A / 230 V

    CEE 16A

    16 A / 230 V

    1533 x 44 x 65 mm
    Show more

    16 A / 230 V / Residual Current Monitoring per supply cable

    16 A / 230 V / Residual Current Monitoring per supply cable

    Number of C13 sockets
    Number of C19 sockets

    Outlets in total

    Slave variant

    For at least 46U server racks

    Plug

    Dimensions

    16 A / 230 V / Residual Current Monitoring per supply cable

    802.3525
    Number of C13 sockets 18
    Number of C19 sockets 4

    16 A / 230 V / Residual Current Monitoring per supply cable

    0

    16 A / 230 V / Residual Current Monitoring per supply cable

    -

    16 A / 230 V / Residual Current Monitoring per supply cable

    -

    16 A / 230 V / Residual Current Monitoring per supply cable

    CEE 16A

    16 A / 230 V / Residual Current Monitoring per supply cable

    1500 x 44 x 65 mm
    Show more

    16 A / 400 V

    16 A / 400 V

    Number of C13 sockets
    Number of C19 sockets

    Outlets in total

    Slave variant

    For at least 46U server racks

    Plug

    Dimensions

    16 A / 400 V

    802.3506
    Number of C13 sockets 18
    Number of C19 sockets 3

    16 A / 400 V

    0

    16 A / 400 V

    -

    16 A / 400 V

    -

    16 A / 400 V

    CEE 16A

    16 A / 400 V

    1500 x 44 x 65 mm

    16 A / 400 V

    802.3508
    Number of C13 sockets 24
    Number of C19 sockets 6

    16 A / 400 V

    0

    16 A / 400 V

    -

    16 A / 400 V

    -

    16 A / 400 V

    CEE 16A

    16 A / 400 V

    1762 x 44 x 65 mm

    16 A / 400 V

    802.3514
    Number of C13 sockets 36
    Number of C19 sockets 6

    16 A / 400 V

    0

    16 A / 400 V

    -

    16 A / 400 V

    +

    16 A / 400 V

    CEE 16A

    16 A / 400 V

    1943 x 44 x 65 mm
    Show more

    16 A / 400 V / Residual Current Monitoring per phase

    16 A / 400 V / Residual Current Monitoring per phase

    Number of C13 sockets
    Number of C19 sockets

    Outlets in total

    Slave variant

    For at least 46U server racks

    Plug

    Dimensions

    16 A / 400 V / Residual Current Monitoring per phase

    802.3522
    Number of C13 sockets 24
    Number of C19 sockets 6

    16 A / 400 V / Residual Current Monitoring per phase

    0

    16 A / 400 V / Residual Current Monitoring per phase

    -

    16 A / 400 V / Residual Current Monitoring per phase

    -

    16 A / 400 V / Residual Current Monitoring per phase

    CEE 16A

    16 A / 400 V / Residual Current Monitoring per phase

    1762 x 44 x 65 mm
    Show more

    32 A / 230 V

    32 A / 230 V

    Number of C13 sockets
    Number of C19 sockets

    Outlets in total

    Slave variant

    For at least 46U server racks

    Plug

    Dimensions

    32 A / 230 V

    802.3520
    Number of C13 sockets 24
    Number of C19 sockets 4

    32 A / 230 V

    0

    32 A / 230 V

    -

    32 A / 230 V

    -

    32 A / 230 V

    CEE 32A

    32 A / 230 V

    1500 x 44 x 65 mm
    Show more

    32 A / 400 V

    32 A / 400 V

    Number of C13 sockets
    Number of C19 sockets

    Outlets in total

    Slave variant

    For at least 46U server racks

    Plug

    Dimensions

    32 A / 400 V

    802.3509
    Number of C13 sockets 24
    Number of C19 sockets 6

    32 A / 400 V

    0

    32 A / 400 V

    -

    32 A / 400 V

    -

    32 A / 400 V

    CEE 32A

    32 A / 400 V

    1762 x 44 x 65 mm
    Show more

    32 A / 400 V / Residual Current Monitoring per phase

    32 A / 400 V / Residual Current Monitoring per phase

    Number of C13 sockets
    Number of C19 sockets

    Outlets in total

    Slave variant

    For at least 46U server racks

    Plug

    Dimensions

    32 A / 400 V / Residual Current Monitoring per phase

    802.3527
    Number of C13 sockets 24
    Number of C19 sockets 6

    32 A / 400 V / Residual Current Monitoring per phase

    0

    32 A / 400 V / Residual Current Monitoring per phase

    -

    32 A / 400 V / Residual Current Monitoring per phase

    -

    32 A / 400 V / Residual Current Monitoring per phase

    CEE 32A

    32 A / 400 V / Residual Current Monitoring per phase

    1945 x 44 x 65 mm
    Show more

    Ask for your desired product!

    Do you need more information about our products and services? Please feel free to contact us.

    map

    Questions? We will help you!

    Do you have questions or would you like a quote? We will be happy to help you.

    It's easy to find your local consultant.

    Telephone number

    +49 711 86602-0

    Applications

    IT Infrastructure

    learn more